Protectowire 2000 FireSystem Bedienungsanleitung Seite 27

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 33
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 26
24
Testing
Inspection, testing and maintenance of all fire
detection/releasing systems shall be per-
formed only by experienced and qualified
personnel. All people and facilities that
receive alarm, trouble or supervisory signals
shall be properly notified prior to the start of
testing and again after the testing has been
concluded. Suppression systems shall be
secured from inadvertent actuation by discon-
necting electric actuators or releasing sole-
noids, closing valves or taking other actions as
appropriate for the specific system for the
duration to the test. All system devices and
releasing components must be returned to
their normal condition after completion of
the system testing.
Classified as a fixed-temperature, non-restor-
able line type heat detector, Protectowire is
subject to the following test method as
described in NFPA 72:
“Do not heat test. Test mechanically and elec-
trically for function. Measure and record loop
resistance. Investigate changes from accep-
tance test.”
This test procedure may be easily accom-
plished in Class B initiating circuits by using
the built-in test button contained in some fac-
tory supplied end-of-line zone boxes, or by
using a jumper wire to apply a short across
the end-of-line resistor to create an alarm. In
a Class A initiating circuit the recommended
procedure is to remove the plus and minus
return legs of the circuit at the control panel
terminals. This action should cause a trouble
signal at the control panel.
To create an alarm condition on the circuit
(alarm overrides trouble), place a jumper
across the disconnected return leads. This
action will cause the necessary alarm condition
to activate the circuit and complete the test.
To measure loop resistance, place each circuit
in alarm and leave the short across the detec-
tion circuit as described above. Disconnect
each detection circuit’s wires from the termi-
nals of the control panel. Place an ohm meter
across the disconnected zone wires (out +
and out –) and record the resistance mea-
sured. Compare these values at each annual
testing. Any change in loop resistance should
be investigated for possible deterioration of
the inner conductors with particular attention
given to termination points, in-line splices or
areas of the Detector where the outer jacket
has been compromised or damaged.
In some areas, local codes or the authority hav-
ing jurisdiction may require a heat test in lieu
of the recommended electrical test procedure.
A simple method of heat testing a non-restor-
able fixed-temperature linear detector, is to
select a convenient location in the detection
loop and using approved splicing connectors or
zone boxes, install a small test length of linear
detector between the splice connection points.
The test area may be heated by what-
ever means required to satisfy the test require-
ments. When finished, the heat actuated section
can be removed and replaced with a new piece
of detector, thereby restoring the system back to
normal operation.
PPrrootteeccttoowwiirree TTeesstt
EEqquuiippmmeenntt
To assist the installer and service personnel in
locating heat actuated sections of the Protecto-
wire Linear Heat Detector, or portions of the
Detector which have been shorted due to
mechanical damage, two portable test instru-
ments are available from The Protectowire
Company.
APL-90 Meter Adapter
The APL-90 Meter Adapter is designed to con-
vert any Digital Multimeter which contains a
200 millivolt scale, to a Protectowire Alarm
Point Location Meter. It enables the user to
determine the distance of the alarm point
(short) from the start of the Protectowire por-
tion of the detection circuit. The APL-90 is
housed in a high impact plastic case which
measures 3.75 x 2.50 x 1 inch (9.5 x 6.4 x 2.5
cm). The unit weighs 4 ounces (113 g), and is
powered by one 9 volt Type 1604 battery,
which provides sufficient power for approxi-
mately 100 hours of use.
The Adapter is equipped with a standard size
double banana plug with male probes spaced
.75 of an inch (1.9 cm) on center. This plug
provides the means to connect into a Digital
Multimeter. A power ON/OFF switch, Power
Seitenansicht 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 33

Kommentare zu diesen Handbüchern

Keine Kommentare