
7
travels freely down the joist channels. However,
heat has trouble spreading across the joists, so
the distance in this direction must be reduced.
The Protectowire shall be mounted on the bot-
tom of the joists, and the spacing of the detector
on all runs measured at right angles parallel to
the joists shall not exceed 50% of the smooth ceil-
ing spacing. On runs that parallel both joists and
walls, the spacing shall not exceed 25%.
Beam Construction
In the case of beam construction where the
beams are 4 inches (100mm) or less in depth,
the ceiling shall be treated the same as a
smooth ceiling. If the beams project more
than 4 inches (100mm) below the ceiling, the
spacing at right angles to the direction of
beam travel shall not exceed two-thirds of the
smooth ceiling spacing. Where the beams
project more than 18 inches (46 cm) below
the ceiling and are spaced more than 8 feet
(2.4 m) on center, each bay formed by the
beams shall be treated as a separate area
requiring detector coverage.
Detector Mounting & Dead Air Space
Heat from a fire rises to the ceiling in a plume
and spreads radially from the fire source. As
the hot gases cool, they begin to bank down
from the ceiling. The corner where the ceiling
and wall meet forms an area known as “dead
air space” as shown in Figure 4. In most fires,
this dead air space is the triangular area
formed along the ceiling by measuring 4 inch-
es (10 cm) out from the corner, and 4 inches
(10 cm) down the side wall. Protectowire
should not be placed in this area.
High Ceiling Considerations
The purpose of this section is to discuss the
effects of ceiling height on the installed spacing
of Protectowire Linear Heat Detector and to
explain the importance of modifying the listed
spacing in order to achieve detector response.
Logic tells us that a detector will ordinarily
operate sooner in detecting a fire if it is clos-
er to the fire source. This is because as smoke
and heat rise from a fire, they do so in a
plume which has the general shape of an
inverted cone. The concentration of smoke
and heat within the cone varies inversely as a
variable function of the distance from the
source. This characteristic is amplified during
the early stages of a fire because the angle of
the plume is wide. As the fire grows in size,
the angle of the plume narrows, which tends
to reduce the effect of ceiling height.
As the ceiling height increases, a larger-size fire
is necessary to actuate the same detector in the
same length of time. As a result of this, system
design practice mandates that the listed spacing
of heat detectors be reduced for the purposes
of providing faster detector response to a fire,
and to increase the likelihood that the detector
will respond to a smaller fire.
To compensate for the effect that high ceiling
installations have on detector performance,
The National Fire Alarm and Signaling Code,
NFPA 72, provides derating factors which can
be applied to the listed spacing of any heat
detector when installed on ceilings 10 to 30
feet (3m to 9.1m) high. These derating factors
are shown as a percentage of the detector’s list-
ed spacing, and have been developed to pro-
vide detector performance on higher ceilings
[to 30 feet (9.1m)] that is equivalent to that of
Figure 3
Figure 4
S
—
4
S
—
2
S
—
2
S
= Max. Listed Spacing
S
Kommentare zu diesen Handbüchern