The Common Alarm Signaling (CAS) Relay provides two sets of contacts for interfacing to other control equipment upon the
initiation of any alarm condition. This relay is normally non-silenceable
but can be field modified to provide silenceable contacts.
%&(*%$
The relays positive terminal (18/24) is sourced with 24V FWR. Once any detection zone is initiated (Alarm State), a “Common
Alarm” negative going output connected to the negative (0) terminal of the relay is activated. The relay is then energized and the
contacts change state. The relay resets when all initiating device zones are reset to the standby condition.
>4931D?B(54
CC-91NT
%@D9?>L)M?==?>*B?E2<5)97>1<9>7(5<1I
)(&*%$
The Common Trouble Signaling (CTS) Relay provides two sets of contacts for interfacing to other control equipment upon any
system trouble or switch supervisory alarm condition. This relay is normally non-silenceable but is field selectable by placing the
jumper “B2” located on the Control Card to the “S” (Silenceable) position. See illustration below.
%&(*%$
When a system fault or supervisory occurs, the Main Board common trouble contacts, used as a pilot, change state de-energizing the
(CTS) relay. The Common Trouble Signaling (CTS) Relay contacts in turn change state until the trouble condition is cleared or reset.
If the control cards “B2” jumper is set at the “S” (Silenceable) position, the relay may be returned to the normal state by depressing
the trouble silence button “Sys./TRO. SIL.” on the control card. Only in this mode will subsequent supervisory alarms cause the
(CTS) relay to reactivate, otherwise the relay will remain de-energized until all system troubles are cleared or reset.
Note A: A label has been added to reconfigure
the contact arrangement of the CTS relay. This is
necessary since the relay is normally energized
and de-energizes in a trouble condition.
>4931D?BB55>
)55$?D5
"*("
"*("
DC Contact Rating 7 amps @ 24VDC
AC Contact Rating 10 amps @ 115VAC
Contact Configuration DPDT
Coil Rating 0.035 amps @ 24VDC
Indicator Red LED
DC Contact Rating 7 amps @ 24VDC
AC Contact Rating 10 amps @ 115VAC
Contact Configuration DPDT
Coil Rating 0.035 amps @ 24VDC
Indicator Green LED